I/P, E/P Transducers

Type 100M

Type 500X

Type 550X

Type 5500

Type 900X

Type 925

Type 950XP

Type 1200

Type 1200 Eltop Electric to Pneumatic Converter
Low power consumption
Failsafe operation in the event of power failure

 

 
 
 
   

Description
Type 1200 electric to pneumatic pressure regulator designed for set point control in all types of flow applications. Type 1200 uses a reversible DC motor to position diaphragm valve operators by converting the DC signal to variable pneumatic output.

Application

  • VALVE POSITIONER/ACTUATOR
  • COMPRESSOR/PUMP
  • "SCADA" OPERATED SYSTEMS
  • DCS OPERATIONS

Back to Top

 

Features
FAIL SAFE OPERATION

ELECTRONICALLY OPERATED WITH REVERSIBLE DC MOTOR

STAINLESS STEEL AND ALUMINUM

IN-LINE FILTER

TEMPERATURE AND ENVIRONMENT RANGES FROM -40° F TO +150° F

CAN USE UP TO 150 PSI SUPPLY OFF FIRST STAGE AIR COMPRESSOR

EASILY SERVICED

VARIETY - 3 MOTOR VARIATIONS AND 6 DIFFERENT CYCLE TIMES

HIGH TORQUE

NO POWER DRAW EXCEPT WHEN MOTOR IS CYCLING BETWWEN SET POINTS

EXPLOSION PROOF (CSA CLASS 1 GROUP D)

CANADIAN STANDARDS ASSOCIATION APPROROVED

 

Back to Top

 

Specifications

Cycle Time

(1 RPM) 12 VDC = 20 min., 28 VDC = 8 min.
(4 RPM) 12 VDC = 4 min., 28 VDC = 1.5 min.
(10 RPM) 12 VDC = 2 min., 28 VDC = 1 min.

Current

60 Milliamperes

Voltage

28 VDC maximum; 11 VDC minimum

Pressure

Maximum Input = 150 PSI,
Minimum output = 30 PSI
maximum & minimum range settings adjustable within the 0-30 PSI range (i.e. 3 to 15 PSI)

Operation

Polarity voltage changes directly control the movement and motor direction between setpoints
NO POWER DRAW REQUIRED, EXCEPT WHEN MOTOR IS CYCLING BETWEEN SET POINTS.

Weight

6 Lb. 4 Oz.


Back to Top

 

Ordering Information

Contact Company for ordering information

 

Back to Top

 

Controlair 康气通中国技术支持及销售中心

地址: 珠海市吉大石花西路42号协和大厦二楼  邮编:519015

Tel : +86-756-333675133367523336753   FAX : +86-756-3336485

© Copyright 2005 ControlAir, Inc.